610 Modbus Registers [new]: Lovato Dmg

Suppose you want to read the total energy consumption data from the DMG 610 using a Modbus master device. You would send a Modbus read command to access the register 40001, which stores the total energy consumption data.

The DMG 610 uses . Most real-time values are stored as 32-bit floating-point numbers (IEEE 754) or 32-bit integers, requiring two consecutive 16-bit registers. Real-Time Voltage & Current Address (Hex) Address (Dec) Voltage L1-N Voltage L2-N Voltage L3-N Voltage L1-L2 Current L1 Current L2 Current L3 Power and Frequency Address (Hex) Address (Dec) Total Active Power Total Reactive Power Total Apparent Power Power Factor (Total) 🔋 Energy Counter Registers lovato dmg 610 modbus registers

| | Solution | |----------------------------------------|------------------------------------------------------------------------------| | Wrong scaling (e.g., 2300 V instead of 230.0 V) | Always apply /10 for voltage, /1000 for current and power. | | Garbage float values | Check byte order – DMG 610 uses AB CD (big-endian). Swap if needed. | | Cannot write to config registers | Write 1 to Reg 4999 first (unlock), then write config, then Reg 4999 = 0 . | | Communication timeout | Verify serial settings match device (often 19200, 8E1 for DMG 610). | Suppose you want to read the total energy

Here are some common Modbus registers used in the Lovato DMG 610: Most real-time values are stored as 32-bit floating-point

| Parameter | Address (Hex) | Data Type | Values | |-----------|---------------|-----------|--------| | CT Primary | 0x1000 | uint16 | 1..9999 | | CT Secondary | 0x1001 | uint16 | 1A or 5A | | VT Primary | 0x1002 | uint16 | 100..500000 V | | VT Secondary | 0x1003 | uint16 | 100V, 110V, 400V, 415V | | System type | 0x1004 | uint16 | 0=3∅ 4 wire, 1=3∅ 3 wire, 2=1∅ 2 wire | | Modbus Slave ID | 0x1005 | uint16 | 1..247 | | Baud rate index | 0x1006 | uint16 | 1=1200, 2=2400, 3=4800, 4=9600, 5=19200, 6=38400 | | Parity | 0x1007 | uint16 | 0=none, 1=odd, 2=even |

Baud Rate: 19200 Data Bits: 8 Parity: Even Stop Bits: 1 Slave ID: 1 Response Timeout: 500 ms